Cold Storage Below Caused Condensation – A Warehouse Full of Goods Destroyed
A storage unit at Nan Fung Industrial City, Tuen Mun, suffered persistent condensation on its floors, ceilings and walls. Cardboard boxes became soggy, paper cups and packaging materials grew mouldy, and furniture was damaged. The owner initially had no idea where the moisture came from. SILVER SURVEYORS investigated and confirmed the cause was condensation (sweating) from the cold storage unit below — not a leak or pipe failure. Our survey report identified the root cause, documented over HK$239,000 in combined repair and stock losses, and provided legally valid evidence for the owner to pursue compensation.
SWEAT (CONDENSATION) TESTING
Cold Storage Below Caused Condensation – A Warehouse Full of Goods Destroyed
Case Background
In August 2019, the owner of a warehouse unit at Nan Fung Industrial City, Tuen Mun, began noticing something strange.
Water droplets kept appearing on the floor, ceiling and walls — day after day. Cardboard boxes were soaked through and softened. Stock placed on the floor started growing mould. Printed logos on packaging blurred and faded. An entire batch of goods looked unsellable.
The owner had never seen this problem before. There was no cracked ceiling, no leaking pipe — yet the water seemed to appear from nowhere.
Worse still, there was no obvious source. Calling a plumber didn't help. The government's seepage team said it wasn't their scope. Meanwhile, thousands of dollars' worth of stock was being ruined day by day.
Eventually, the owner learned that the unit directly below had been leased to a frozen food company and converted into a cold storage room, running large freezers at very low temperatures around the clock.
To get to the truth and prepare for a potential claim, the owner engaged SILVER SURVEYORS to investigate.
What We Found On Site
We arrived at the unit on 30 October 2019. The air inside was heavy with moisture.
Floors, ceiling and walls were covered with water droplets
All cardboard boxes — containing paper cups, paper bags, cake boxes, napkins and other packaging materials — were damp and softening
White mould had formed on some shelves
The affected area spanned approximately 2,000 sq. ft.
We used infrared thermal imaging to scan the surfaces. The results showed widespread trapped moisture hidden within the ceiling and walls. We collected water samples for testing and checked every visible pipe in the unit — all supply pipes and fire service pipes were exposed and showed no signs of leakage.
The Truth: Not a Leak, But Condensation
Many people assume "water equals leak". In this case, it was different.
The real cause was temperature difference:
The cold storage unit below was kept at extremely low temperatures for long periods. The warmer, humid air in the upper unit met the cold floor slab and walls — exactly like stepping outside an air-conditioned room on a hot summer day. Moisture instantly condensed into droplets. This is called "condensation" or "sweating".
We ruled out all other possibilities:
No rain on the inspection day → not rainwater penetration
Water sample tested fresh (low salinity, negative for ammonia) → not seawater or sewage
All pipes were exposed and dry → no plumbing leak
No typical water stains or peeling paint on the ceiling → not a conventional leak
The conclusion: the owner's own unit was not at fault. The water was being "chilled out of the air" by the cold storage below.
The Outcome
Our survey report provided clear, legally admissible findings:
Confirmed the water was condensation caused by temperature differential between the two units
Identified the root cause: insufficient insulation and excessively low temperature in the cold storage unit below
Documented affected area: approximately 2,000 sq. ft. covering floor, ceiling and walls
Estimated structural repair cost (including plastering, anti-rust treatment, painting): approximately HK$49,436
Assessed damaged stock (paper cups, lids, napkins, paper bags, cake boxes, coasters, greeting cards, chairs, etc.): approximately HK$189,739
Total combined loss: approximately HK$239,175
With this report, the owner no longer had to say "I don't know what caused it". He could present scientific evidence to the cold storage tenant and relevant parties, and use the report to support an insurance claim.
Our Takeaway
Some water doesn't come from a broken pipe — it comes from the air itself.
The hardest part isn't wiping away the droplets. It's watching perfectly good stock turn mouldy and worthless, without being able to prove who is responsible.
At SILVER SURVEYORS, we don't just measure moisture. We help business owners identify invisible causes, calculate real losses, and recover what they are rightfully owed — step by step.
SILVER SURVEYORS – Leakage investigation service
We provide independent investigation and surveying services for all types of water leakage cases – including external wall seepage, upper-floor leakage, burst pipes, sewage backflow, ceiling dripping, and structural water ingress. Using infrared thermography, smoke testing, moisture metering, water sample analysis and other scientific methods, we accurately trace the source and deliver court‑admissible loss assessment reports. Whether it's a residential flat, shop or office, we help you get the facts straight, the numbers right, and the compensation you deserve.
Have a leakage problem? Contact Silver Surveyors. We'll listen to your situation first, then tell you what to do next.
📞 Inquiry Hotline:3489 9268 / 6608 4330
📱 WhatsApp:+852 5423 3828
🌐 Official Website:www.silversurveyor.org
📩 Inquiries welcome; free initial consultation.


















Expertise
Impartial evaluations and certifications for construction projects.
Integrity
Quality
Tel: +852 3489 9268 (general inquiry)
+65183092
+66084330
Fax: +852 3460 0214
Mobile: +852 6518 3092
Wtsapp +852 5423 3828
Email: info@silversurveyor.org
© 2025. All rights reserved.